Graphic Operation Terminal F940GOT Additional Functions (V 4.10/5.00 or later) 17
17-3
17.3 Connection to PLC manufactured by Siemens
17.3.1 Direct connection to CPU
Connected PLC
Direct connection to CPU (RS-232C)
For connection, the HMI adapter is required. (Refer to the connection example shown
below.)
However, 416-1 and 416-2DP do not support some devices.
For the details, refer to the Operation Manual of F940GOT-E offered separately.
Setting of PLC
Set the MPI address of the PLC connected to the GOT using the programming software
(STEP7) for the S7-300/400 Series PLC.
The MPI address of the HMI adapter is "1", and the maximum MPI address is "31".
Accordingly, make sure to set the MPI address of the PLC inside the range from 2 to 31.
Setting of GOT
Set the connected PLC, the connection type and the station No. as shown below.
Table 17.4:
Applicable CPU
S7-300 Series 312IFM, 313, 314IFM, 315, 315-2DP, 316
S7-400 Series 412-1, 413-1, 413-2DP, 414-1, 414-2DP, 416-2DP
Table 17.5:
MPI address
Personal computer (for
programming)
0 (fixed in MPI network)
HMI adapter 1 (fixed)
PLC 2 to 31
Table 17.6:
PLC TYPE SIEMENS S7-300
CONNECTION CPU PORT (RS232C)
STATION #
MPI address (2 to 31) set in PLC
Have in mind that station Nos. "0" and "1" are treated as "2".