'10 • SR-T-091
Installation dimensions
Hanging bolt pitch
Hanging bolt pitch
Plan
35 35
740
670
455
515
30
30
Side
Liquid side pipes
Gas side pipes
Drain hose
(Connection opening diameter ø16)
150
455
38
236
135
78
Front
30
740 106
230 11
Mounting of interconnecting wires (Field wiring)
Remove the control lid.
Connect the connection wire securely to the terminal block.
Preparations for the main frame
Use cables for interconnection wiring to avoid loosening
of the wires.
CENELEC code for cables Required field cables.
H05RNR4G1.5 (Example)
H Harmonized cable type
05 300/500 volts
R Natural-and/or synth. rubber wire insulation
N Polychloroprene rubber conductors insulation
R Stranded core
4 Number of conductors
G
One conductor of the cable is the earth conductor
(yellow/green)
1.5 Section of copper wire (mm
2
)
1) Connect the connection wire securely to the terminal
block. If the wire is not affixed completely, contact will
be poor, and it is dangerous as the terminal block may
heat up and catch fire.
2) Take care not to confuse the terminal numbers for
indoor andoutdoor connections.
3) Affix the connection wire using the wiring clamp.
Attach the control lid.
Clamp
Control lid
Terminal block
INSTALLATION OF INDOOR UNIT
Drilling of holes in the wall and fixture of sleeve
The connecting wires may touch the metal inside the wall and cause danger so it is necessary to
always use the sleeve.
Indoor side
Outdoor side
Drill a hole with a 65 whole
core drill.
Sleeve
Sleeve
Wall thickness + 15
(unit : mm)
Sealing plate
Inclination plate
Pipe
Assembled state
φ65
When the pipe is connected at the rear, cut off the lower and the right side
portions of the sleeve collar (as shown by the broken line).
2
Securing the ceiling hanging bolts
If steel embedded ceiling
Inserts
Holed anchor
Holed plug
Hanging bolts M8
Concrete
If wooden ceiling
Holes for ceiling hanging bolts
Square bars for hanging the air conditioner
Clamps
Beams
Secure the ceiling hanging
bolts firmly following the
illustrations and other
instructions.
Installing the main unit
Attach the washers and nuts to the ceiling hanging bolts.
Attach the hanging tool to the above nuts, and tighten the nuts.
M8 large washer
M8 nut
M8 handling bolt
M8 nut
(standard accessory)
M8 large washer
M8 spring lock washer
(standard accessory)
Main frame
Securing the wireless receiver
About the option parts
If it is not leveled, the float switch may malfunction or may not start.
Unit main body
Filter guide
Air filter
Plate (display)
Flat head
machine screw
Flat head
machine screw
(In the pack of )
Installation frame
Wireless receiver
Cut off this section if it interferes with the wall.
CalkingCalking
Open a through-hole on the wall to install the reception face for the wireless receiver .
Insert the wireless receiver in the installation frame , and fix the calking section.
Fix the installation frame on the wall using the flat head machine screws .
Fix the plate (display) on the installation frame using the flat head machine screws packed together
with the plate (display) .
Cut off this section if it interferes
with the wall.