8. Special functions
8.3. Refrigerant collecting (pump down) (Fig. 8-3)
The refrigerant collecting function is available by performing the following procedure.
1 Close the 2 liquid stop valves and the cylinder/hydro unit side gas valve.
Only the indoor unit side gas valve remains open.
2 Connect the 2 gas stop valve service ports with a hose.
3 Turn on the main power and wait for 3-4 minutes.
4 Press the SWP button on the outdoor controller board, then the refrigerant collecting operation starts.
5 After con rming the low pressure is lowered to 0 MPa (gauge), close the indoor unit side gas valve.
The refrigerant collecting operation stops automatically in 5 minutes.
6 Turn off the main power.
Warning:
Do not disconnect extension pipes during the refrigerant collecting operation is running.
If you open the stop valves to the air during the compressor is running, the pressure could be abnormal high level and this may cause a rupture
of the compressor or other hazardous situation.
* Use a refrigerant recovery machinery if the refrigerant collecting is not completed in case of long pipe length or too much refrigerant contained.
Fig. 8-3
Stop valve
Hose
4-way valve
SV3 SV1 SV2
TH4
TH3
* SV1/SV2/SV3 are closed when the power is not supplied.
TH6
LEV-A
LEV-CLEV-B
TH34
Muffler
Compressor
Stop valve
Stop valve
Indoor
UNIT
Cylinder/
Hydrobox
UNIT
Service port
Service port
Accumulator
Service port
Stop valve
Service port
Charge
plug
Charge plug
High pressure
sensor(63HS)
High pressure
switch (63H)
Seitenansicht 10
1 2 ... 6 7 8 9 10 11 12 13 14 15

Kommentare zu diesen Handbüchern

Keine Kommentare