  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 7
8
Perform the airtight test, vacuum air purging,
additional refrigerant charging (if necessary),
and gas leak check.
4.7. Precautions when reusing existing R22 refrigerant pipes
• Refer to the owchart below to determine if the existing pipes can be used and if it is necessary to use a lter dryer.
• If the diameter of the existing pipes is different from the speci ed diameter, refer to technological data materials to con rm if the pipes can be used.
Measure the existing pipe thickness and
check for damage.
The existing pipe thickness meets speci ca-
tions and the pipes are not damaged.
Check if the existing air conditioner can operate.
After operating the cooling system for about 30
minutes, do a pump down work.
Disconnect the existing air conditioner from the
pipes.
Attach the new air conditioner
Test run
* Refer to 7.2.
The existing pipes cannot be reused.
Use new pipes.
* If the existing air conditioner cannot operate, use
a refrigerant recovery device to collect the refrigerant.
* If the existing pipes are used for gas or oil heat
pump systems, use new pipes.
The existing pipe thickness does not meet
speci cations or the pipes are damaged.
4. Installing the refrigerant piping
Drain socket PAC-SG61DS-E
Drain pan PAC-SG64DP-E
5. Drainage piping work
Outdoor unit drainage pipe connection
When drain piping is necessary, use the drain socket or the drain pan (option).
4.8. For twin indoor units combination (Fig. 4-7)
When this unit is used as a FREE COMPO MULTI unit, install the refrigerant
piping with the restrictions indicated in the drawing on the left. In addition, if the
restrictions are going to be exceeded, or if there are going to be combinations of
indoor and outdoor units, refer to installation instructions for the indoor unit for
details about the installation.
Indoor unit
Outdoor unit
Multi distribution pipe (option)
Height difference (Indoor unit-
Outdoor unit) Max. 20 m
Height difference (Indoor unit-
Indoor unit) Max. 1 m
A: Main piping
B, C: Branch piping
<Limits of refrigerant piping installation>
A+B+C 30 m
Permissible total piping length
A+B+C
30 m or less
Charge-less piping length
A+B+C
30 m or less
|
B-C
|
No. of bends
Within 15
8 m or less
Including Cylinder- or Hydrobox-side pipe length
Fig. 4-7