'10 • SR-T-091D
1. SPECIFICATIONS
(1) Wall mounted type (SRK)
B
RWA000Z 225
Model
Item
SRK50ZJ-S
Indoor unit SRK50ZJ-S Outdoor unit SRC50ZJ-S
Cooling capacity (1) W 5000 (1600 (Min.)
~
5500 (Max.))
Heating capacity (1) W 5800 (1600 (Min.)
~
6600 (Max.))
Power supply 1 Phase, 220
~
240 V, 50Hz
Operation
data (1)
Power
consumption
Cooling
kW
1.55 (0.40
~
2.20)
Heating 1.59 (0.42
~
2.10)
Running
current
Cooling
A
7.1 / 6.8 / 6.5 (220/ 230/ 240 V)
Heating 7.3 / 7.0 / 6.7 (220/ 230/ 240 V)
Inrush current 7.3 / 7.0 / 6.7 (220/ 230/ 240 V)
COP
Cooling 3.23
Heating 3.65
Noise
level
Cooling
Sound level dB(A) Hi : 46 Me : 37 Lo : 26 51
Power level dB 61 61
Heating
Sound level dB(A) Hi : 45 Me : 37 Lo : 31 53
Power level dB 61 63
Exterior dimensions (Height x Width x Depth) mm 294 x 798 x 229 640 x 800 (+71) x 290
Exterior appearance
(Munsell color)
Fine snow
( 8.0Y 9.3/0.1 ) near equivalent
Stucco white
( 4.2Y 7.5/1.1 ) near equivalent
Net weight kg 9.5 42
Refrigerant
equipment
Compressor type & Q'ty 5RS132XAB21 (Rotary type) x 1
Motor (Starting method) kW 0.90 (Line starting)
Refrigerant oil 0.37 (FV50S)
Refrigerant (4) kg R410A 1.35 (Pre-Charged up to the piping length of 15m)
Heat exchanger Louver fins & inner grooved tubing M fins & inner grooved tubing
Refrigerant control Capillary tubes + Electronic expansion valve
Deice control Microcomputer control
Air handling
equipment
Fan type & Q'ty Tangential fan x 1 Propeller fan x 1
Motor W 38 34
Air flow
Cooling
CMM
Hi : 11.3 Me : 7.8 Lo : 5.3 36.0
Heating Hi : 13.5 Me : 10.2 Lo : 7.5 36.0
Fresh air intake Not possible
Air filter, Quality / Quantity Polypropylene net (washable) x 2
Shock & vibration absorber Cushion rubber (for compressor)
Electric heater
Operation
control
Operation switch Wireless-Remote control
Room temperature control Microcomputer thermostat
Operation Display RUN : Green, TIMER : Yellow, HI POWER : Green, 3D AUTO : Green
Safety devices
Compressor overheat protection, Overcurrent protection,
Frost protection, Serial signal error protection, Indoor fan motor error protection,
Heating overload protection (High pressure control), Cooling overload protection
Installation
data
Refrigerant piping size (O.D) mm Liquid line :
φ
6.35 (1/4") Gas line :
φ
12.7 (1/2")
Connecting method Flare connecting
Attached length of piping m
Liquid line : 0.53
Gas line : 0.40
Insulation for piping Necessary (Both sides), independent
Refrigerant line (one way) length
m
Max. 25
Vertical height difference between
outdoor unit and indoor unit
Max. 15 (Outdoor unit is higher)
Max. 15 (Outdoor unit is lower)
Drain hose Connectable (VP16)
Power cable
Recommended breaker size A 16
Connection wiring
Size x Core number 1.5mm
2
x 4 cores (Including earth cable)
Connecting method Terminal block (Screw fixing type)
Accessories (included)
Mounting kit, Clean filter (Allergen clear filter x 1, Photocatalytic washable deodorizing filter x 1)
Optional parts Interface kit (SC-BIKN-E)
Note (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature Outdoor air temperature
Standards
DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
ISO-T1, JIS C 9612
Heating 20˚C 7˚C 6˚C
(2) This air-conditioner is manufactured and tested in conformity with the ISO.
(3) The operation data are applied to the 220/230/240V districts respectively.
(4) The refrigerant quantity to be charged includes the refrigerant in 15m connecting piping.
(Purging is not required even for the short piping.)
The pipe length is 7.5m.
Adapted to RoHS directive
Downloaded from AC-Manual.com Manuals