2
-
’10 • SC-T-154
1 CENTRAL CONTROL SC-SL2N-E
(1) Specification
Definitions of new and previous Super Link (new and previous SL)
New Super Link (new SL): All units connected to the network are models compatible with New Super Link
(KXE6 model or later models. Central controller and I/F are from “N” models.) and
SL setting is unchanged from shipment (“New” or “AUTO”).
Previous Super Link (previous SL): Units do not meet the conditions of New SL. When even a single unit connected to
the network is an earlier model than KXE4 or the connected model is not compatible
with New SL. Setting explained in Note (5) is required.
Appearance
Notes (1) Some of functions may not be used depending on the indoor unit. (See page 4 (2).)
(2) For the specification of relay being procured at site, select a product that can assure the minimum application load of DC 12 V, 10 mA or less.
Even if it is reset within 2 minutes after input, the input state is retained.
(3) For the specification of relay being procured at site, select a product with the rated voltage at DC 12 V, max. power consumption at DC 0.9 W or
under (80 mA or under).
(4) Dimension +35 in ( ) indicates the embedded dimension.
(5) When the connecting network consists of previous Super Link, it is necessary to set the control selector switch SW5 to OFF.
(Factory default is ON.)
Description
Model name
Applicable model
Ambient temperature in operation
Power supply
Power consumption
External dimensions (HWD)
Net weight
Max. number of connectable indoor units
CENTRAL CONTROL SC-SL2NA-E
SC-SL2NA-E
Super Link compatible indoor unit
(1)
0 ~ 40˚C
1 phase, 100 ~ 240 V, 50/60 Hz
7W
120mm215mm(2535)mm
(4)
1kg
New SL: Max. 64 units, previous SL: Max. 48 units
1 point, Non-voltage contact “a” input
(Open
/
Close: RUN, Close
/
Open: STOP)
1 point, Non-voltage contact point “a” input,
continuous input
(Close; Center & Stop all units)
1 point, Non-voltage contact “a” input,
continuous input
(Close: Center & Fan mode)
All indoor units at STOP; Open
If there is any unit operating; Close
All indoor units normal: Open
If there is any abnormal unit; Close
Input
Output
External timer input
(2)
Emergency stop signal input
(2)
Demand signal input
(2)
Operation output
(3)
Error output
(3)
PJZ000Z281
Seitenansicht 0
1 2 3 4 5 6 7 8

Inhaltsverzeichnis

Seite 1 - 1 CENTRAL CONTROL SC-SL2N-E

- 2 -’10 • SC-T-1541 CENTRAL CONTROL SC-SL2N-E(1) SpecificationDefinitions of new and previous Super Link (new and previous SL) New Super Link (new S

Seite 2 - ’10 • SC-T-154

- 3 -’10 • SC-T-154CENTER / REMOTE displayDisplays which is in effect, the central control or the local remote controllers.PROGRAM SET displayDisplaye

Seite 3 - (3) Status monitor

- 4 -’10 • SC-T-154Notes (1) Don’t use the auto mode on any indoor unit other than those connected to the simultaneous heating & cooling 3-pipe s

Seite 4 - (4) Program setting

- 5 -’10 • SC-T-154Item DescriptionGroup settingIndividual settingTime & date settingAlarm historyDemand controlEmergency stopPower restoration co

Seite 5 - (8) Electrical wiring

- 6 -’10 • SC-T-154(7) Installation procedure(a) In case of embedding in a wall, first, embed the power supply wire, signal wire, and electrical box.

Seite 6 - (9) Installation work

- 7 -’10 • SC-T-154Wiring OutlineWiring specifications(9) Installation workPlease install the central control after turning off the power for fear of

Seite 7 - 1 2 3 4 5 6 7 8 9 10 11 12

- 8 -’10 • SC-T-154(c) In case of installing on the control boardPlease be sure to lock the control board to protect persons from the electric shock.

Seite 8

- 9 -’10 • SC-T-154(10) Control switch selectionIt is possible to change the setting as follows by settings of the PCB switches SW1 to SW10, J1, J2,