’10 • SC-T-154
Notes (1) Don’t use the auto mode on any indoor unit other than those connected to the simultaneous heating & cooling 3-pipe system or single PAC.
(2) Do not set the set point at 0.5˚C intervals in case this product is used with RCD type wired remote controller.
It would cause malfunction of the wired remote controller. Please make sure to set at 1˚C intervals.
(3) This function can be applied to the indoor units, which are the model KXE4 or later, SC-ADN-E or later and to the remote controller, which is the model
RC-E1 or later. (For models earlier than the above-mentioned, the function becomes invalid because the indoor unit and remote controller cannot receive
the instruction even though the setting can be displayed.)
Since setting is overwritten in SL2NA-E even if setting is done from the remote controller, set using SL2NA-E.
(4) This function can be applied to the indoor units, which are the model KXE6D or later, SC-ADNA-E or later.
For the previous indoor units, it is not possible to set the 4th mode but other setting is possible as before.
4th fan speed setting is “impossible” before shipment, so changing to “possible” is needed for 4th fan speed setting from this Central control.
4th fan mode of indoor units operating at 4th fan mode can be displayed on SC-SL2NA-E whose 4th fan mode setting is “impossible”.
(SW7 changes “possible” or “impossible” for 4th fan mode setting from SC-SL2NA-E.)
“Possible” needs the indoor units, which are the model KXE6D or later, SC-ADNA-E or later.
Item Description
RUN/STOP
Operation mode
Temperature setting
Center/remote
Fan speed
Fan direction
Filter reset
Error reset
No.
1
2
3
4
5
6
7
8
9
Individual Lock/Unlock settings enabled in
Function Setting of remote controller.
Performs operation or stop control.
Sets Auto
(1)
, Cool, Dry, Fan or Heat.
Sets temperature in the range of 18 ~ 30˚C (0.5˚C interval)
(2)
Sets the center, remote or center remote.
Sets 4
th
, 3
rd
, 2
nd
, 1
st
speed.
Sets the auto swing ON/OFF and positions 1 ~ 4.
Controls the filter sign reset.
Puts out the error sign with the RUN or STOP operation
SC-SL2NA-E (before shipment)
SC-SL2NA-E (SW7 is ON)
SC-SL2N-E (old model)
4th fan speed settiing
Impossible
Possible
Impossible
4th fan speed display
Possible
Possible
Impossible
Sets the permission/prohibition on the basis of remote controller function.
Sets the permission or prohibition for RUN/STOP control, operation mode setting,
temperature setting or each functions.
(3)
Notes (1) If “Check” button is pressed when the icon is turned on by 8, 9 and 10, display will change automatically to the display of corresponding unit No.
When 8, 9 and 10 are mixed, 10 takes the highest priority. When all of 10 is reset, display is in the order of 9 to 8.
(2)
When the operation time exceeds 9,800 hours, it displays Inspection 2 and, if it exceeds 10,000 hours, Inspection 1 is displayed. (GHP only)
Item Description
RUN/STOP status
Operation mode
Temperature setting
Room temperature
Fan speed
Fan direction
Filter sign
No.
1
2
3
4
5
6
7
8
9
10
Displays the operation mode of unit No. on display.
Displays the setting temperature of unit No. on display.
Displays the suction temperature of unit No. on display.
Monitors the RUN/STOP status of unit No. on display.
With LED for each group, it monitors the RUN/STOP status of each group.
When the filter cleaning time is exceeded on one or more indoor units, the filter
sign icon is turned on. When it corresponds to the unit No. on display, the icon
blinks.
When there is one or more indoor units requiring maintenance, the maintenance
icon is turned on.
There are 4 types of operation of Inspection, Inspection 1, Inspection 2 and Back up.
Inspection :There is an indoor unit requiring maintenance.
Inspection1 :The operation time (GHP outdoor unit) exceeds 10000 hours
Inspection2 :The operation time (GHP outdoor unit) exceeds 9800 hours
Backup :Connected outdoor unit is on backup operation.
Preference order of display is as shown below.
Backup > Inspection 1 > Inspection 2 > Inspection
When it corresponds to the unit No. on display, the icon blinks.
When any error is detected on one or more controlled indoor units, the error icon
is turned on. If it corresponds to the unit No. on display, the icon blinks and the
display shows the error code, date/time of error occurrence, connected outdoor
unit No. (KXE6 type or later).
Maintenance
(2)
,
(Inspection, Inspection 1, Inspection 2 and
Backup)
Permission/prohibition on the basis of
remote controller function
Displays the status of permission/prohibition setting for each remote controller
function of unit No. on display.
Display the permission/prohibition of the RUN/STOP control, operation mode
setting and temperature setting.
Permission/prohibition setting for each function as set from the remote controller
is not reflected because it is overwritten from SC-SL2NA-E.
Trouble (Error)
Displays the fan speed of unit No. on display.
Displays the auto swing ON/OFF setting and position setting of unit No. on display.
(2) Operation and setting
Operation or setting is implemented individually, in the unit of group or in a batch for air-conditioners up to 64 units or 16 groups.
(3) Status monitor
Status monitor may be applied in the unit of group or air-conditioner.