SERVICE MANUAL
CONTENTS
1. TECHNICAL CHANGES ··································· 3
2. PART NAMES AND FUNCTIONS ····················· 4
3. SPECIFICATION ················································ 5
4. NOISE CRITERIA CURVES ······························ 7
5. OUTLINES AND DIMENSIONS ························ 8
6. WIRING DIAGRAM ············································ 9
7. REFRIGERANT SYSTEM DIAGRAM ··············11
8. PERFORMANCE CURVES ····························· 13
9. ACTUATOR CONTROL ··································· 24
10. SERVICE FUNCTIONS ···································· 25
11. TROUBLESHOOTING ····································· 25
12. DISASSEMBLY INSTRUCTIONS ···················· 40
Models
SPLIT-TYPE AIR CONDITIONERS
MUZ-HC25VA -
E1
MUZ-HC35VA -
E1
MUZ-HC35VA -
E2
MUZ-HC35VAB -
E1
MUZ-HC35VAB -
E2
HFC
utilized
R410A
No. OBH467
REVISED EDITION-B
OUTDOOR UNIT
Indoor unit service manual
MSZ-HC•VA Series (OBH466)
MSZ-CHC•VA Series (OBH522)
NOTE:
RoHS compliant products have <G> mark on the spec name plate.
PARTS CATALOG (OBB467)
Revision B:
• MUZ-HC35VA-
E2
and MUZ-HC35VAB-
E2
have
been added.
Please void OBH467 REVISED EDITION-A.
Seitenansicht 0
1 2 3 4 5 6 ... 43 44

Inhaltsverzeichnis

Seite 1 - OUTDOOR UNIT

SERVICE MANUALCONTENTS1. TECHNICAL CHANGES ··································· 32. PART NAMES AND FUNCTIONS ····················· 43. SPECIFICATION ··

Seite 2 - Revision B:

10MUZ-HC35VA-E2 MUZ-HC35VAB-E2

Seite 3 - TECHNICAL CHANGES

11Unit : mmOutdoorheatexchangerFlared connectionDefrostthermistorRT61DischargetemperaturethermistorRT62Flared connectionStop valve(with strainer)Stop

Seite 4 - PART NAMES AND FUNCTIONS

12MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCERefrigerant piping: mPiping size O.D: mmMax. LengthAMax. Height differenceBGas LiquidMUZ-HC

Seite 5 - SPECIFICATION

13The standard specifications apply only to the operation of the air conditioner under normal conditions. Since operating condi-tions vary according t

Seite 6

14Indoor intake air Dry-bulb temperature (°C)Outdoor intake air Wet-bulb temperature (°C) Outdoor intake air Wet-bulb temperature (°C) Indoor intake a

Seite 7 - NOISE CRITERIA CURVES

150 50 100 150(Hz)0.00.51.01.50 50 100 150(Hz)0.00.51.01.50 50 100 150(Hz)0.00.51.01.52.00 50 100 150(Hz)0.00.51.01.52.00 50 100 150

Seite 8 - OUTLINES AND DIMENSIONS

16kgf/cm2 [Gauge]MPa [Gauge]183215 205025603070 (%)35(°C)323070 (%)35(°C)0.20.40.60.81.01.224681012141.4Ambient temperature (°C)

Seite 9 - WIRING DIAGRAM

17PERFORMANCE DATA COOL operation at Rated frequencyMUZ-HC25VACAPACITY: 2.5 kW SHF: 0.79 INPUT: 770 WINDOORDB (°C)INDOORWB (°C)OUTDOOR DB (°C)21 25

Seite 10 - MUZ-HC35VAB

18PERFORMANCE DATA COOL operation at Rated frequencyMUZ-HC25VACAPACITY: 2.5 kW SHF: 0.79 INPUT: 770 WINDOORDB (°C)INDOORWB (°C)OUTDOOR DB (°C)35 40

Seite 11 - REFRIGERANT SYSTEM DIAGRAM

19PERFORMANCE DATA COOL operation at Rated frequencyMUZ-HC35VACAPACITY: 3.15 kW SHF: 0.76 INPUT: 980 WINDOORDB (°C)INDOORWB (°C)OUTDOOR DB (°C)21 2

Seite 12

2Revision A:•Table “ADDITIONAL REFRIGERANT CHARGE” of “7. REFRIGERANT SYSTEM DIAGRAM” has been corrected.Revision B:• MUZ-HC35VA-E2 and MUZ-HC35VAB-E2

Seite 13 - PERFORMANCE CURVES8

20PERFORMANCE DATA COOL operation at Rated frequencyMUZ-HC35VACAPACITY: 3.15 kW SHF: 0.76 INPUT: 980 WINDOORDB (°C)INDOORWB (°C)OUTDOOR DB (°C)35 4

Seite 14 - defrost operation

21PERFORMANCE DATA COOL operation at Rated frequencyMUZ-HC35VABCAPACITY: 3.4 kW SHF: 0.76 INPUT: 1130 WINDOORDB (°C)INDOORWB (°C)OUTDOOR DB (°C)21

Seite 15

22PERFORMANCE DATA COOL operation at Rated frequencyMUZ-HC35VABCAPACITY: 3.4 kW SHF: 0.76 INPUT: 1130 WINDOORDB (°C)INDOORWB (°C)OUTDOOR DB (°C)35

Seite 16

23PERFORMANCE DATA HEAT operation at Rated frequencyMUZ-HC25VACAPACITY: 3.2 kW INPUT: 880 WINDOORDB (°C)OUTDOOR WB (°C)-10 -5 0 5 10 15 20Q INPUT Q

Seite 17 - MUZ-HC25VA

24MUZ-HC25VA MUZ-HC35VA MUZ-HC35VAB9-2. R.V. COIL CONTROLHeating . . . . . . . . . . . . . . . . . ON Cooling . . . . . . . . . . . . . . . . . OFFD

Seite 18

2510-1. CHANGE IN DEFROST SETTING <JS> When the JS wire of the inverter P.C. board is cut/ soldered, the defrost finish temperature is changed.

Seite 19

26Outline of the functionThis air conditioner can memorize the abnormal condition which has occurred once.Even though LED indication listed on the tro

Seite 20

27 2. Flow chart of the detailed outdoor unit failure mode recall function 2.Blinking pattern when outdoor unit is abnormal:ONOFFNo beepBeepsRepeat

Seite 21

28 3. Outdoor unit failure mode tableThe upper lamp of OPERATION INDICTOR lamp (Indoor unit) Abnormal point (Failure mode / protection) LED indicatio

Seite 22

2911-3. TROUBLESHOOTING CHECK TABLENo. Symptom LED indication Abnormal point / Condition Condition Correspondence 1Outdoor unit does not oper-ate. 1-

Seite 23 - MUZ-HC35VA MUZ-HC35VAB

3MUZ-HA25VA -E1 → MUZ-HC25VA -E1MUZ-HA35VA -E1 → MUZ-HC35VA -E1MUZ-HA35VA -E1 → MUZ-HC35VAB -E1 1. Outdoor model has been changed.MUZ-HC35VA -E1

Seite 24 - ACTUATOR CONTROL

3011-4. TROUBLE CRITERION OF MAIN PARTSMUZ-HC25VA MUZ-HC35VA MUZ-HC35VABPart name Check method and criterion FigureDefrost thermistor(RT61) Measur

Seite 25 - SERVICE FUNCTIONS

3111-5. TROUBLESHOOTING FLOWAre the voltages balanced?Disconnect the connector (CN61) between compressor and the intelligent power module (IPM).Replac

Seite 26

32Refer to 11-5. “Check of compressor operation time”.Does the compressor operate continuously?Refer to 11-5. “Check of compressor start failure”.OK

Seite 27 - Operational procedure

33 F Check of compressor start failureAfter the compressor is heated with a drier, does the compressor start? 1Replace the compressor.Compressor sta

Seite 28

34 H Check of R.V. coil First of all, measure the resistance of R.V. coil to check if the coil is defective. Refer to 11-4. In case CN721 is not conn

Seite 29 - Flashing

35 J Check of power supplyIs there voltage 230 VAC between the indoor terminal block S1 and S2?NoYesReplace the indoor electronic control P.C. board.

Seite 30

36Replace the indoor power P.C. board and the indoor terminal P.C. board K How to check miswiring and serial signal errorTurn OFF the power supply.Is

Seite 31 - B Check of open phase

37Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor

Seite 32 - C Check of compressor

38 M Electromagnetic noise enters into TV sets or radiosYesIs the unit earthed?NoEarth the unit.YesIs the distance between the antennas and the indoo

Seite 33

39-20 -10 0 10 20 30 400102030405060708090100Temperature (°C)Defrost thermistor (RT61)Temperature (°C)Discharge temperature thermistor (RT62)0 1020304

Seite 34 - H Check of R.V. coil

4ACCESSORIESAir outletDrain outletPipingDrain hoseAir inletMUZ-HC25VA MUZ-HC35VA MUZ-HC35VABDrain socket 12PART NAMES AND FUNCTIONS

Seite 35 - J Check of power supply

4012-1. MUZ-HC25VA MUZ-HC35VA MUZ-HC35VABNOTE: Turn OFF power supply before disassembling.OPERATING PROCEDURE PHOTOS1. Removing cabinet and panels(1

Seite 36

41OPERATING PROCEDURE PHOTOS2. Removing the inverter assembly, inverter P.C. board(1) Remove the cabinet and panels. (Refer to 1.)(2) Disconnect the e

Seite 37

42OPERATING PROCEDURE PHOTOS5. Removing outdoor fan motor(1) Remove the cabinet and panels. (Refer to 1.)(2) Disconnect the connectors for outdoor fan

Seite 39 - 1. Inverter P.C. board

HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN Copyright 2007 MITSUBISHI ELECTRIC ENGINEERING CO.,LTDDistributed in Au

Seite 40 - DISASSEMBLY INSTRUCTIONS

5Outdoor model MUZ-HC25VA MUZ-HC35VA MUZ-HC35VAB Function Cooling Heating Cooling Heating Cooling Heating Power supply Single phase 230 V, 50 Hz Ca

Seite 41 - OPERATING PROCEDURE PHOTOS

6Specifi cations and rating conditions of main electric partsModel Item MUZ-HC25MUZ-HC35VA- E1 MUZ-HC35VAB- E1MUZ-HC35VA- E2 MUZ-HC35VAB- E2Current tra

Seite 42

790807060504030201063 125 250 500 1000 2000 4000 8000NC-60NC-50NC-40NC-30NC-20NC-70OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BARBAND CENTER

Seite 43

820.8144.689.6255145.5Service panelService portAir outLiquid refrigerant pipe jointRefrigerant pipe (flared) ø6.35Gas refrigerant pipe jointRefrigeran

Seite 44

9MUZ-HC25VA MUZ-HC35VA-E1 MUZ-HC35VAB-E16WIRING DIAGRAM