Mitsubishi Q62DAN Bedienungsanleitung Seite 28

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 144
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 27
1 - 13 1 - 13
MELSEC-Q
1 GENERAL SPECIFICATIONS AND PRECAUTIONS FOR USE OF I/O
MODULE
1.2.5 Interrupt module
(1) If setting the response time during the interrupt input operation of QI60 or QX40H,
QX70H, QX80H, and QX90H, use the module whose contents are shown below.
The response time cannot be set with other contents (fixed at 0.2ms.).
Product name Contents
PLC CPU Product information "021120000000000-B" or later
GX Developer SW6D5C-GPPW or later
For how to check product information of the CPU module, refer to QCPU User's
Manual (Hardware Design, Maintenance and Inspection).
1.2.6 Installation and wiring
(1) Insulation-sleeved-solderless terminals cannot be used with the terminal block.
It is recommended to cover the wire connections of the solderless terminals with
mark or insulation tubes.
(2) Use wires of 0.3 to 0.75mm
2
core and 2.8mm (0.11in.) OD max. to connect to the
terminal block. When using a wire whose core is 0.75mm or more, it is preferable to
use the spring clamp terminal block(Q6TE-18S).
(3) Tighten the module fixing and terminal block screws to the torques in the following
ranges.
Screw location Tightening torque range
Module fixing screw (M3 12 screw) 36 to 48 N•cm
I/O module terminal block screw (M3 screw) 42 to 58 N•cm
I/O module terminal block mounting screw (M3 screw) 66 to 89 N•cm