CONTENTS1. TECHNICAL CHANGES····································22. PART NAMES AND FUNCTIONS······················33. SPECIFICATION···················
10 Both indoor and outdoor units are under the same temperature/humidity condition.OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENTCOOL operation Air f
118-2. Trouble criterion of main parts$$:INNER PROTECTORTROUBLESHOOTING88-1. Cautions on troubleshooting1. Before troubleshooting, check the following
12DISASSEMBLY INSTRUCTIONS9OPERATING PROCEDUREPHOTOSPhoto 11. Removing the cabinet(1) Remove the screws fixing the top panel. (See Photo 1.)(2) Remove
133. Removing the propeller and the outdoor fan motor(1) Remove the cabinet. (Refer to 1.)(2) Remove the propeller nut and the propeller.NOTE : Loose
14OPERATING PROCEDURE PHOTOS4. Removing the compressor(1) Remove the cabinet. (Refer to 1.)(2) Remove the soundproof felt.(3) Remove the screws fixing
152. Removing the electrical parts(1) Remove the service panel and the cabinet. (Refer to 1.)(2) Remove the following parts.•Compressor capacitor (C1)
16PHOTOSOPERATING PROCEDURE3. Removing propeller and the outdoor fan motor(1) Remove the cabinet. (Refer to 1.)(2) Remove the propeller nut and remove
17PHOTOSOPERATING PROCEDURE4. Removing the compressor(1) Remove the cabinet. (Refer to 1.)(2) Remove the relay panel.(3) Remove the soundproof felt.(4
2TECHNICAL CHANGES1MU-A08ND- C2 = MU-GD08ND- C11. Compressor has been changed. (2R10S3R236A-6B = KS-098NARC)2. Outdoor fan motor has been changed. (
MITSUBISHI ELECTRIC CONSUMER PRODUCTS (THAILAND) CO., LTD.AMATA NAKORN INDUSTRIAL ESTATE 700/406 MOO 7, TAMBON DON HUA ROH, AMPHUR MUANG, CHONBURI 200
32PART NAMES AND FUNCTIONSAir outletDrain outletPipingDrain hose Air inlet(back and side)MU-C08VCMU-C10VCMU-C13VCMU-C18VC Air inlet(back and s
4SPECIFICATION3Outdoor modelMU-GD08ND - C1MU-GD10ND - C1MU-GD12ND - C1Function CoolingPower supplySingle phase220-230V, 60HzCapacityCapacity kW 2.2-2.
54OUTLINES AND DIMENSIONS20.86.4416.98255145.5Service panelService portAir outLiquid refrigerant pipe jointRefrigerant pipe (flared) ;6.35Gas refriger
6WIRING DIAGRAM5MU-C08VCMU-C10VCMU-C13VCMU-GD08NDMU-GD10ND
7MU-C18VCREFRIGERANT SYSTEM DIAGRAM6Refrigerant flow in coolingCapillary tubeX3.0 ' X 1.6 ' 650 CompressorStop valve(with service port)Stop
8MAX.REFRIGERANT PIPING LENGTHModel Piping size O.D : mmRefrigerant piping : mGasX9.52LiquidX6.352010MU-GD08ND-Max. lengthAMax. heightBMU-GD10ND-MU-GD
9PERFORMANCE CURVES7The standard data contained in these specifications apply only to the operation of the air conditioner under normal conditions.Sin